• Home
  • Low Voltage Switchgear

Motor Control Centers

Be it a Building or an Industrial application, the Motors are an integral & significant part of the electrical loads. The Motor Control Centers are required to operate motors at the installation. Every motor load is configured to switch ON/OFF as per the pre-defined engineering conditions. The outgoing feeders in an MCC perform the Switching & starting of motors through one of the type of starting methodologies available.

  • Rating
    Up to 4000A at 690V, 50Hz
  • Short Circuit Rating
    50kA 3 sec / 85kA 1 sec & 100 kA 1 sec
  • Type of construction
    Up to Form 4B, IP54, Fixed or With-drawable construction with Front & Rear or Front access options. Available with DOL/Star-Delta/VFD / Soft Starter feeders as per Type2 coordination, as applicable. Control Panels for switching of individual motor loads in internal (IP42) or external application (IP65) are also available.
  • Operating Ambient Temperature
    Up to 50 Deg C
  • Type Test Certification
    Type tested up to 4000A rating, 100kA 1sec, for compliance to IEC614391 & 2